Address: Plot-14(Level-6), Main Road, Block-C, Banasree, Rampura, Dhaka-1219, Bangladesh.
Latest Update
We Are Hiring! | Senior Sales Executive
Technical Directory
Featured

Technical Directory

Access our full collection of product catalogs, technical manuals, and ISO certificates.

Browse Resources
TR Capacity Calculator
Featured

TR Capacity Calculator

Not sure which AC capacity fits your room? Use our precision tool to calculate the exact tonnage you need.

Calculate Now
Our Global Partners
Featured

Our Global Partners

Authorized distributor of world-renowned HVAC and building automation brands.

View All Brands
Project Showcases
Featured

Project Showcases

Explore our portfolio of successfully delivered industrial HVAC projects.

View Gallery
Join Our Force
Featured

Join Our Force

Become part of Bangladesh's leading HVAC engineering team.

See Openings
ELITE TECHNICAL SPECIFICATION

Hitachi Magnetic Bearing Centrifugal Chiller VM Series

TECHNICAL SPECIFICATION OVERVIEW

Oil free worry free/Highly efficient/Stable & Reliable

The Hitachi VM series is a magnetic-bearing centrifugal chiller that utilizes magnetic levitation technology to achieve a frictionless and non-contact levitation state. VM chillers utilize magnetic bearings to support the spinning rotor of the compressor and leverage centrifugal force to compress refrigerant gas. The compressed gas is used to cool air or water, making the VM series an efficient and reliable cooling solution.

Hitachi VM Series (Turbocor) Mechanical Diagram

High Efficiency Oil-free Magnetic-Bearing Chiller

The Hitachi magnetic-bearing centrifugal compressor is designed to maximize energy efficiency and reliability. One of the key features of this chiller compressor is its high-speed direct transmission design, which eliminates the need for speed-increasing gears and reduces transmission loss. Another important feature of the Hitachi magnetic bearing centrifugal compressor is its use of magnetic bearings instead of traditional mechanical bearings. This eliminates the need for lubricating oil, which reduces mechanical loss and maintenance requirements. Combined with Hitachi's high-efficiency closed-type two-stage impeller, the VM series centrifugal chiller achieves a high level of energy efficiency. In fact, under standard GB operating conditions, the chiller can achieve a full load COP as high as 7.0 and an IPLV as high as 9.5. Magnetic bearing technology offers several advantages over traditional oil-lubricated bearing solutions. It uses magnetic fields to levitate the rotor, eliminating the need for physical contact between the rotor and stator. This oil-free operation not only simplifies the system's structure but also reduces the energy losses caused by friction in traditional bearings. Moreover, magnetic bearings have no mechanical wear and tear, reducing chiller maintenance requirements and increasing system reliability. They also eliminate the need for complex oil lubrication systems in chillers, which can be costly to maintain and negatively impact heat exchanger efficiency. By utilizing a permanent magnet motor as a direct-drive impeller instead of a conventional gear-based system, the compressor achieves a simpler transmission mechanism with fewer moving parts, which significantly reduces the failure rate and enhances reliability. The adoption of a permanent magnet motor leads to a reduction of up to 66% in the number of delicate and consumable parts compared to a conventional compressor.

Request Senior HVAC Consultation

Need professional consulting for Hitachi VM Series (Turbocor)? Contact The Aircons Ltd. team today to speak with our senior HVAC application engineers.

Speak with our Engineers
Hitachi VM Series (Turbocor) Features Overview

Easy Maintenance Chiller with Permanent Magnet Motor with Low-noise & Safe & Carefree Operation

The magnetic-bearing centrifugal chiller unit has a standard emergency power-off protection system. If a power failure happens, the permanent magnet motor will rotate inertially to generate electricity and apply brakes. The energy produced is then stored in the frequency converter and used to power the magnetic bearing, maintaining the shaft's suspension state until the unit comes to a complete stop. This helps to prevent the shaft from falling directly onto the bearing and potentially damaging the magnetic chiller unit's lifespan. When evaluating the impact of a chiller unit on the environment, noise is an important factor to consider. The VM series centrifugal chiller unit adopts magnetic bearings, which completely suspend the moving parts and eliminate friction during operation. This results in a low operating noise of only 76dB(A), which is 5-10 decibels less than that of ordinary centrifugal chillers. Lower noise levels create a more comfortable environment in the computer room, allowing operators to control the system more effectively. The absence of a lubricating oil system in this magnetic-bearing chiller unit significantly reduces maintenance costs by eliminating the need for oil replacement, oil filter replacement, dryer replacement, replacement parts, and associated labor costs. Meanwhile, this oil-free chiller unit features a pre-mounted inverter panel, and all the necessary wiring between the components is completed at the factory. This design eliminates the need for additional power and control wiring between the inverter panel and the chiller unit, which would typically require extra investment from the customer. Additionally, the integrated inverter panel saves installation space in the machine room.

Operational Excellence & Long-term Viability

The Hitachi VM series magnetic-bearing centrifugal chiller is a highly efficient, oil-free cooling solution that utilizes magnetic levitation and a direct-drive permanent magnet motor to eliminate gears and lubrication. This frictionless design delivers a full-load COP of 7.0 and an IPLV of 9.5, while reducing consumable parts by up to 66%. Featuring an integrated, factory-wired inverter panel, an automatic kinetic energy braking safety system, and an ultra-low noise profile of 76 dB(A), the VM series significantly lowers installation, maintenance, and energy costs while maximizing system reliability. As a trusted partner, The Aircons Ltd. proudly supplies authentic Hitachi VM series chillers. Working in close collaboration with Hitachi, The Aircons Ltd. delivers international-quality engineering solutions, providing expert system design, seamless installation, and comprehensive support to ensure your cooling infrastructure operates at peak performance.

Frequently Asked Questions

The VM series utilizes a high-speed direct-drive design with proprietary magnetic bearings rather than traditional mechanical bearings. This frictionless design eliminates the need for speed-increasing gears and a complex lubricating oil system.
Extremely efficient. Under GB standard working conditions, the combination of the magnetic bearings and a high-efficiency two-stage impeller allows the chiller to achieve a full-load COP as high as 6.81 and an Integrated Part Load Value (IPLV) of up to 9.29.
No, the unit is protected. It comes standard with an emergency power-off protection system. During a power failure, the permanent magnet motor uses its rotational inertia to act as a generator. The electricity generated is fed back to the magnetic bearings, keeping the shaft suspended safely until the unit comes to a complete stop
Yes. The compressor includes custom-designed ceramic auxiliary (protective) bearings. If the compressor drops out of its magnetic suspension, the shaft will land directly on these robust ceramic bearings, avoiding any damage to the magnetic bearings themselves.
It is exceptionally quiet. Because the magnetic bearings suspend the moving parts and eliminate mechanical friction, the operating noise is as low as 76 dB(A). This is 5 to 10 decibels quieter than standard centrifugal units.
An oil-free system is much easier and cheaper to maintain. It completely eliminates the maintenance tasks associated with traditional lubrication systems, such as replacing oil, swapping oil filters, and replacing dryers. Furthermore, it stops lubricating oil from coating the heat exchanger, which typically degrades efficiency over time.

Technical Parameters & Engineering Specifications

Engineering ParameterDesign Value / Operating Metric
Product SeriesHitachi VM Series Magnetic Bearing Centrifugal Chiller
Compressor TypeMagnetic bearing inverter centrifugal compressor with single shaft direct drive
RefrigerantR134a
Cooling Capacity (Single Unit)350 - 1100 RT
Efficiency (GB Standard)COP up to 6.81; IPLV up to 9.29
Operating NoiseAs low as 76 dB(A)
Recommended Power SupplyAC 380V / 50Hz / 3-phase / 3W
Voltage LimitsRated running voltage ±10%; Voltage Imbalance ≤2%
Load Limit Range5% - 100%
Water Side Pressure Resistance1.0 MPa (Standard); 1.6 MPa and 2.0 MPa (Optional)
Maximum Water Flow RateShould not exceed 3.0 m/s
Control Panel Display10-inch color liquid crystal touch display
Remote CommunicationRS485 physical bus using MODBUS RTU format
Operating Ambient Temperature3°C - 40°C (Chiller plant room)
Operating Relative Humidity<80% (without condensing water)
Operating Altitude<1000 meters (High altitudes require special adjustments)

Explore Related Brand Specifications

Magnetic Bearing Centrifugal Chillers

Dunham-Bush Prometheus / DCLC-M

Industrial Optimized technical specifications and engineering limits.

View Specifications
Magnetic Bearing Centrifugal Chillers

York YZ Series

Industrial Optimized technical specifications and engineering limits.

View Specifications

Deploy Elite HVAC Systems

Ready to deploy Hitachi VM Series (Turbocor) at your facility? Let our certified elite technical team engineer a custom blueprint for you.

Get a Technical Proposal

Ready to Engineer?

Require precise technical specifications, CAD data, or a professional consultation for your next infrastructure project?